pyidf.hvac_design_objects module¶
Data objects in group “HVAC Design Objects”
-
class
pyidf.hvac_design_objects.DesignSpecificationOutdoorAir¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object DesignSpecification:OutdoorAir This object is used to describe general outdoor air requirements which are referenced by other objects.
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
outdoor_air_flow_air_changes_per_hour¶ field Outdoor Air Flow Air Changes per Hour
This input should be used if the field Outdoor Air Method is AirChanges/Hour.This input is used if the field Outdoor Air Method is AirChanges/Hour, Sum, or MaximumUnits: 1/hrParameters: value (float) – value for IDD Field Outdoor Air Flow Air Changes per Hour Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_flow_air_changes_per_hour or None if not set Return type: float
-
outdoor_air_flow_per_person¶ field Outdoor Air Flow per Person
0.00944 m3/s is equivalent to 20 cfm per personThis input should be used if the field Outdoor Air Method is Flow/Person.This input is used if the field Outdoor Air Method is Flow/Person, Sum, or MaximumUnits: m3/s-personDefault value: 0.00944Parameters: value (float) – value for IDD Field Outdoor Air Flow per Person Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_flow_per_person or None if not set Return type: float
-
outdoor_air_flow_per_zone¶ field Outdoor Air Flow per Zone
This input should be used if the field Outdoor Air Method is Flow/Zone.This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or MaximumUnits: m3/sParameters: value (float) – value for IDD Field Outdoor Air Flow per Zone Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_flow_per_zone or None if not set Return type: float
-
outdoor_air_flow_per_zone_floor_area¶ field Outdoor Air Flow per Zone Floor Area
This input should be used if the field Outdoor Air Method is Flow/Area.This input is used if the field Outdoor Air Method is Flow/Area, Sum, or MaximumUnits: m3/s-m2Parameters: value (float) – value for IDD Field Outdoor Air Flow per Zone Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_flow_per_zone_floor_area or None if not set Return type: float
-
outdoor_air_flow_rate_fraction_schedule_name¶ field Outdoor Air Flow Rate Fraction Schedule Name
Schedule values are multiplied by the Outdoor Air Flow rate calculated usingthe previous four inputs. Schedule values are limited to 0 to 1.Parameters: value (str) – value for IDD Field Outdoor Air Flow Rate Fraction Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_flow_rate_fraction_schedule_name or None if not set Return type: str
-
outdoor_air_method¶ field Outdoor Air Method
Flow/Person => Outdoor Air Flow per Person * Occupancy = Design Flow Rate,Flow/Area => Outdoor Air Flow per Zone Floor Area * Zone Floor Area = Design Flow Rate,Flow/Zone => Outdoor Air Flow per Zone = Design Flow Rate,AirChanges/Hour => Outdoor Air Flow Air Changes per Hour * Zone Volume adjusted for m3/s = Design Flow RateDefault value: Flow/PersonParameters: value (str) – value for IDD Field Outdoor Air Method Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_method or None if not set Return type: str
-
-
class
pyidf.hvac_design_objects.DesignSpecificationZoneAirDistribution¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object DesignSpecification:ZoneAirDistribution This object is used to describe zone air distribution in terms of air distribution effectiveness and secondary recirculation fraction. It is referenced by Sizing:Zone and Controller:MechanicalVentilation objects
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
zone_air_distribution_effectiveness_in_cooling_mode¶ field Zone Air Distribution Effectiveness in Cooling Mode
Units: dimensionlessDefault value: 1.0Parameters: value (float) – value for IDD Field Zone Air Distribution Effectiveness in Cooling Mode Raises: ValueError– if value is not a valid valueReturns: the value of zone_air_distribution_effectiveness_in_cooling_mode or None if not set Return type: float
-
zone_air_distribution_effectiveness_in_heating_mode¶ field Zone Air Distribution Effectiveness in Heating Mode
Units: dimensionlessDefault value: 1.0Parameters: value (float) – value for IDD Field Zone Air Distribution Effectiveness in Heating Mode Raises: ValueError– if value is not a valid valueReturns: the value of zone_air_distribution_effectiveness_in_heating_mode or None if not set Return type: float
-
zone_air_distribution_effectiveness_schedule_name¶ field Zone Air Distribution Effectiveness Schedule Name
optionally used to replace Zone Air Distribution Effectiveness in Cooling andHeating ModeParameters: value (str) – value for IDD Field Zone Air Distribution Effectiveness Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of zone_air_distribution_effectiveness_schedule_name or None if not set Return type: str
-
zone_secondary_recirculation_fraction¶ field Zone Secondary Recirculation Fraction
Units: dimensionlessParameters: value (float) – value for IDD Field Zone Secondary Recirculation Fraction Raises: ValueError– if value is not a valid valueReturns: the value of zone_secondary_recirculation_fraction or None if not set Return type: float
-
-
class
pyidf.hvac_design_objects.DesignSpecificationZoneHvacSizing¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object DesignSpecification:ZoneHVAC:Sizing This object is used to describe general scalable zone HVAC equipment sizing which are referenced by other objects.
-
cooling_design_capacity¶ field Cooling Design Capacity
Enter the design cooling capacity. Required field when the cooling design capacity methodCoolingDesignCapacity.Units: WParameters: value (float or “Autosize”) – value for IDD Field Cooling Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_capacity or None if not set Return type: float or “Autosize”
-
cooling_design_capacity_method¶ field Cooling Design Capacity Method
Enter the method used to determine the cooling design capacity for scalable sizing.None is used when a cooling coils is not included in the Zone HVAC Equipment orthis field may be blank. If this input field is left blank, then the design coolingcapacity is set to zero. CoolingDesignCapacity => selected when the design cooling capacityvalue is specified or auto-sized. CapacityPerFloorArea => selected when the design coolingcapacity is determine from user specified cooling capacity per floor area and zone floor area.FractionOfAutosizedCoolingCapacity => is selected when the design cooling capacity isdetermined from a user specified fraction and the auto-sized design cooling capacity.Default value: NoneParameters: value (str) – value for IDD Field Cooling Design Capacity Method Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_capacity_method or None if not set Return type: str
-
cooling_design_capacity_per_floor_area¶ field Cooling Design Capacity Per Floor Area
Enter the cooling design capacity per zone floor area. Required field when the cooling designcapacity method field is CapacityPerFloorArea.Units: W/m2Parameters: value (float) – value for IDD Field Cooling Design Capacity Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_capacity_per_floor_area or None if not set Return type: float
-
cooling_fraction_of_autosized_cooling_supply_air_flow_rate¶ field Cooling Fraction of Autosized Cooling Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate.Required field when Cooling Supply Air Flow Rate Method isFractionOfAutosizedCoolingAirflow.This field may be blank if a cooling coil is not included in the Zone HVAC equipment.Parameters: value (float) – value for IDD Field Cooling Fraction of Autosized Cooling Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of cooling_fraction_of_autosized_cooling_supply_air_flow_rate or None if not set Return type: float
-
cooling_supply_air_flow_rate¶ field Cooling Supply Air Flow Rate
Enter the magnitude of supply air volume flow rate during cooling operation.Required field when Cooling Supply Air Flow Rate Method is SupplyAirFlowRate.This field may be blank if a cooling coil is not included in the Zone HVAC equipment.Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Cooling Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate or None if not set Return type: float or “Autosize”
-
cooling_supply_air_flow_rate_method¶ field Cooling Supply Air Flow Rate Method
Enter the method used to determine the cooling supply air volume flow rate.None is used when a cooling coil is not included in the Zone HVAC Equip or this fieldmay be blank. SupplyAirFlowRate => selected when the magnitude of the supply air volumeflow rate is specified. FlowPerFloorArea => selected when the supply air volume flow rateis determined from total floor area served by the Zone HVAC unit and Flow Per Floor Areavalue specified. FractionOfAutosizedCoolingAirflow => is selected when the supply air volumeis determined from a user specified fraction and the autosized cooling supply air flow ratevalue determined by the simulation. FlowPerCoolingCapacity => is selected when the supplyair volume is determined from user specified flow per Cooling Capacity and Cooling Capacitydetermined by the simulation.Default value: SupplyAirFlowRateParameters: value (str) – value for IDD Field Cooling Supply Air Flow Rate Method Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate_method or None if not set Return type: str
-
cooling_supply_air_flow_rate_per_floor_area¶ field Cooling Supply Air Flow Rate Per Floor Area
Enter the cooling supply air volume flow rate per total conditioned floor area.Required field when Cooling Supply Air Flow Rate Method is FlowPerFloorArea.This field may be blank if a cooling coil is not included in the Zone HVAC equipment.Units: m3/s-m2Parameters: value (float) – value for IDD Field Cooling Supply Air Flow Rate Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate_per_floor_area or None if not set Return type: float
-
cooling_supply_air_flow_rate_per_unit_cooling_capacity¶ field Cooling Supply Air Flow Rate Per Unit Cooling Capacity
Enter the cooling supply air volume flow rate unit cooling capacity.Required field when Cooling Supply Air Flow Rate Method isFlowPerCoolingCapacity. This field may be blank if a cooling coil is notincluded in the Zone HVAC equipment.Units: m3/s-WParameters: value (float) – value for IDD Field Cooling Supply Air Flow Rate Per Unit Cooling Capacity Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate_per_unit_cooling_capacity or None if not set Return type: float
-
fraction_of_autosized_cooling_design_capacity¶ field Fraction of Autosized Cooling Design Capacity
Enter the fraction of auto-sized cooling design capacity. Required field when the coolingdesign capacity method field is FractionOfAutosizedCoolingCapacity.Parameters: value (float) – value for IDD Field Fraction of Autosized Cooling Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of fraction_of_autosized_cooling_design_capacity or None if not set Return type: float
-
fraction_of_autosized_heating_design_capacity¶ field Fraction of Autosized Heating Design Capacity
Enter the fraction of auto-sized heating design capacity. Required field when capacity theheating design capacity method field is FractionOfAutosizedHeatingCapacity.Parameters: value (float) – value for IDD Field Fraction of Autosized Heating Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of fraction_of_autosized_heating_design_capacity or None if not set Return type: float
-
heating_design_capacity¶ field Heating Design Capacity
Enter the design heating capacity. Required field when the heating design capacity methodHeatingDesignCapacity.Units: WParameters: value (float or “Autosize”) – value for IDD Field Heating Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_capacity or None if not set Return type: float or “Autosize”
-
heating_design_capacity_method¶ field Heating Design Capacity Method
Enter the method used to determine the heating design capacity for scalable sizing.None is used when a heating coil is not included in the Zone HVAC Equipment orthis field may be blank. If this input field is left blank, then the design heatingcapacity is set to zero. HeatingDesignCapacity => selected when the design heating capacityvalue is specified or auto-sized. CapacityPerFloorArea => selected when the design coolingcapacity is determine from user specified heating capacity per flow area and zone floor area.FractionOfAutosizedHeatingCapacity => is selected when the design heating capacity isdetermined from a user specified fraction and the auto-sized design heating capacityDefault value: NoneParameters: value (str) – value for IDD Field Heating Design Capacity Method Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_capacity_method or None if not set Return type: str
-
heating_design_capacity_per_floor_area¶ field Heating Design Capacity Per Floor Area
Enter the heating design capacity per zone floor area. Required field when the heating designcapacity method field is CapacityPerFloorArea.Units: W/m2Parameters: value (float) – value for IDD Field Heating Design Capacity Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_capacity_per_floor_area or None if not set Return type: float
-
heating_fraction_of_heating_supply_air_flow_rate¶ field Heating Fraction of Heating Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the heating supply air flow rate.Required field when Heating Supply Air Flow Rate Method isFractionOfAutosizedHeatingAirflow.This field may be blank if a heating coil is not included in the Zone HVAC equipment.Parameters: value (float) – value for IDD Field Heating Fraction of Heating Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of heating_fraction_of_heating_supply_air_flow_rate or None if not set Return type: float
-
heating_supply_air_flow_rate¶ field Heating Supply Air Flow Rate
Enter the magnitude of the supply air volume flow rate during heating operation.Required field when Heating Supply Air Flow Rate Method is SupplyAirFlowRate.This field may be blank if a heating coil is not included in the Zone HVAC equipment.Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Heating Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate or None if not set Return type: float or “Autosize”
-
heating_supply_air_flow_rate_method¶ field Heating Supply Air Flow Rate Method
Enter the method used to determine the heating supply air volume flow rate.None is used when a heating coil is not included in the Zone HVAC Equipment or this field maybe blank. SupplyAirFlowRate => selected when the magnitude of the heating supply air volumeflow rate is specified. FlowPerFloorArea => selected when the supply air volume flow rate isdetermined from total floor area served by a Zone HVAC unit and user specified value of FlowPer Floor Area. FractionOfAutosizedHeatingAirflow => is selected when the supply air volumeis determined from a user specified fraction and the Autosized heating supply air flow ratevalue determined by the simulation. FlowPerHeatingCapacity => is selected when the supplyair volume is determined from user specified flow per Heating Capacity and Heating Capacitydetermined by the simulation.Default value: SupplyAirFlowRateParameters: value (str) – value for IDD Field Heating Supply Air Flow Rate Method Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate_method or None if not set Return type: str
-
heating_supply_air_flow_rate_per_floor_area¶ field Heating Supply Air Flow Rate Per Floor Area
Enter the heating supply air volume flow rate per total conditioned floor area.Required field when Heating Supply Air Flow Rate Method is FlowPerFloorArea.This field may be blank if a heating coil is not included in the Zone HVAC equipment.Units: m3/s-m2Parameters: value (float) – value for IDD Field Heating Supply Air Flow Rate Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate_per_floor_area or None if not set Return type: float
-
heating_supply_air_flow_rate_per_unit_heating_capacity¶ field Heating Supply Air Flow Rate Per Unit Heating Capacity
Enter the supply air volume flow rate per unit heating capacity.Required field when Heating Supply Air Flow Rate Method isFlowPerHeatingCapacity.This field may be blank if a heating coil is not included in the Zone HVAC equipment.Units: m3/s-WParameters: value (float) – value for IDD Field Heating Supply Air Flow Rate Per Unit Heating Capacity Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate_per_unit_heating_capacity or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
no_load_fraction_of_cooling_supply_air_flow_rate¶ field No Load Fraction of Cooling Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate.Required field when No Load Supply Air Flow Rate Methodis FractionOfAutosizedCoolingAirflow.Parameters: value (float) – value for IDD Field No Load Fraction of Cooling Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of no_load_fraction_of_cooling_supply_air_flow_rate or None if not set Return type: float
-
no_load_fraction_of_heating_supply_air_flow_rate¶ field No Load Fraction of Heating Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the heating supply air flow rate.Required field when No Load Supply Air Flow Rate Methodis FractionOfAutosizedHeatingAirflow.Parameters: value (float) – value for IDD Field No Load Fraction of Heating Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of no_load_fraction_of_heating_supply_air_flow_rate or None if not set Return type: float
-
no_load_supply_air_flow_rate¶ field No Load Supply Air Flow Rate
Enter the magnitude of the supply air volume flow rate during when no cooling or heatingis required. Required field when No Load Supply Air Flow Rate Methodis SupplyAirFlowRate.Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field No Load Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of no_load_supply_air_flow_rate or None if not set Return type: float or “Autosize”
-
no_load_supply_air_flow_rate_method¶ field No Load Supply Air Flow Rate Method
Enter the method used to determine the supply air volume flow rate When No Cooling or Heatingis Required. None is used when a cooling or heating coil is not included in the Zone HVACEquipment or this field may be blank. SupplyAirFlowRate => selected when the magnitude of thesupply air volume flow rate is specified. FlowPerFloorArea => selected when the supply airvolume flow rate is determined from total floor area served by the Zone HVAC unit and Flow PerFloor Area is specified. FractionOfAutosizedCoolingAirflow => is selected when the supplyair volume is determined from a user specified fraction and the Autosized cooling supplyair flow rate value determined by the simulation. FractionOfAutosizedHeatingAirflow => isselected when the supply air volume is determined from a user specified fraction and theAutosized heating supply air flow rate value determined by the simulation.Default value: SupplyAirFlowRateParameters: value (str) – value for IDD Field No Load Supply Air Flow Rate Method Raises: ValueError– if value is not a valid valueReturns: the value of no_load_supply_air_flow_rate_method or None if not set Return type: str
-
no_load_supply_air_flow_rate_per_floor_area¶ field No Load Supply Air Flow Rate Per Floor Area
Enter the supply air volume flow rate per total floor area.Required field when No Load Supply Air Flow Rate Methodis FlowPerFloorArea.Units: m3/s-m2Parameters: value (float) – value for IDD Field No Load Supply Air Flow Rate Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of no_load_supply_air_flow_rate_per_floor_area or None if not set Return type: float
-
-
class
pyidf.hvac_design_objects.OutputControlSizingStyle¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object OutputControl:Sizing:Style Default style for the Sizing output files is comma – this works well for importing into spreadsheet programs such as Excel(tm) but not so well for word processing programs – there tab may be a better choice. Fixed puts spaces between the “columns”
-
column_separator¶ field Column Separator
Parameters: value (str) – value for IDD Field Column Separator Raises: ValueError– if value is not a valid valueReturns: the value of column_separator or None if not set Return type: str
-
-
class
pyidf.hvac_design_objects.SizingParameters¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object Sizing:Parameters Specifies global heating and cooling sizing factors/ratios. These ratios are applied at the zone level to all of the zone heating and cooling loads and air flow rates. Then these new loads and air flow rates are used to calculate the system level flow rates and capacities and are used in all component sizing calculations. Specifies the width (in load timesteps) of a moving average window which is used to smooth the peak load across more than one timestep.
-
cooling_sizing_factor¶ field Cooling Sizing Factor
Default value: 1.0Parameters: value (float) – value for IDD Field Cooling Sizing Factor Raises: ValueError– if value is not a valid valueReturns: the value of cooling_sizing_factor or None if not set Return type: float
-
heating_sizing_factor¶ field Heating Sizing Factor
Default value: 1.0Parameters: value (float) – value for IDD Field Heating Sizing Factor Raises: ValueError– if value is not a valid valueReturns: the value of heating_sizing_factor or None if not set Return type: float
-
timesteps_in_averaging_window¶ field Timesteps in Averaging Window
blank => set the timesteps in averaging window toNumber of Timesteps per Hour resulting in a 1 hour averaging windowdefault is number of timesteps for 1 hour averaging windowvalue >= 1Parameters: value (int) – value for IDD Field Timesteps in Averaging Window Raises: ValueError– if value is not a valid valueReturns: the value of timesteps_in_averaging_window or None if not set Return type: int
-
-
class
pyidf.hvac_design_objects.SizingPlant¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object Sizing:Plant Specifies the input needed to autosize plant loop flow rates and equipment capacities. This information is initially used by components that use water for heating or cooling such as hot or chilled water coils to calculate their maximum water flow rates. These flow rates are then summed for use in calculating the Plant Loop flow rates.
-
coincident_sizing_factor_mode¶ field Coincident Sizing Factor Mode
this is used to adjust the result for coincident sizing by applying a sizing factorParameters: value (str) – value for IDD Field Coincident Sizing Factor Mode Raises: ValueError– if value is not a valid valueReturns: the value of coincident_sizing_factor_mode or None if not set Return type: str
-
design_loop_exit_temperature¶ field Design Loop Exit Temperature
Units: CParameters: value (float) – value for IDD Field Design Loop Exit Temperature Raises: ValueError– if value is not a valid valueReturns: the value of design_loop_exit_temperature or None if not set Return type: float
-
loop_design_temperature_difference¶ field Loop Design Temperature Difference
Units: deltaCParameters: value (float) – value for IDD Field Loop Design Temperature Difference Raises: ValueError– if value is not a valid valueReturns: the value of loop_design_temperature_difference or None if not set Return type: float
-
loop_type¶ field Loop Type
Parameters: value (str) – value for IDD Field Loop Type Raises: ValueError– if value is not a valid valueReturns: the value of loop_type or None if not set Return type: str
-
plant_or_condenser_loop_name¶ field Plant or Condenser Loop Name
Enter the name of a PlantLoop or a CondenserLoop objectParameters: value (str) – value for IDD Field Plant or Condenser Loop Name Raises: ValueError– if value is not a valid valueReturns: the value of plant_or_condenser_loop_name or None if not set Return type: str
-
sizing_option¶ field Sizing Option
if Coincident is chosen, then sizing is based on HVAC Sizing Simulations andthe input field called Do HVAC Sizing Simulation for Sizing Periods in SimulationControl must be set to YesDefault value: NonCoincidentParameters: value (str) – value for IDD Field Sizing Option Raises: ValueError– if value is not a valid valueReturns: the value of sizing_option or None if not set Return type: str
-
zone_timesteps_in_averaging_window¶ field Zone Timesteps in Averaging Window
this is used in the coincident sizing algorithm to apply a running average to peak flow ratesthat occur during HVAC Sizing SimulationsDefault value: 1value >= 1Parameters: value (int) – value for IDD Field Zone Timesteps in Averaging Window Raises: ValueError– if value is not a valid valueReturns: the value of zone_timesteps_in_averaging_window or None if not set Return type: int
-
-
class
pyidf.hvac_design_objects.SizingSystem¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object Sizing:System Specifies the input needed to perform sizing calculations for a central forced air system. System design air flow, heating capacity, and cooling capacity will be calculated using this input data.
-
a_100_outdoor_air_in_cooling¶ field 100% Outdoor Air in Cooling
Default value: NoParameters: value (str) – value for IDD Field 100% Outdoor Air in Cooling Raises: ValueError– if value is not a valid valueReturns: the value of a_100_outdoor_air_in_cooling or None if not set Return type: str
-
a_100_outdoor_air_in_heating¶ field 100% Outdoor Air in Heating
Default value: NoParameters: value (str) – value for IDD Field 100% Outdoor Air in Heating Raises: ValueError– if value is not a valid valueReturns: the value of a_100_outdoor_air_in_heating or None if not set Return type: str
-
airloop_name¶ field AirLoop Name
Parameters: value (str) – value for IDD Field AirLoop Name Raises: ValueError– if value is not a valid valueReturns: the value of airloop_name or None if not set Return type: str
-
central_cooling_capacity_control_method¶ field Central Cooling Capacity Control Method
Method used to control the coil’s outputDefault value: OnOffParameters: value (str) – value for IDD Field Central Cooling Capacity Control Method Raises: ValueError– if value is not a valid valueReturns: the value of central_cooling_capacity_control_method or None if not set Return type: str
-
central_cooling_design_supply_air_humidity_ratio¶ field Central Cooling Design Supply Air Humidity Ratio
Units: kgWater/kgDryAirDefault value: 0.008Parameters: value (float) – value for IDD Field Central Cooling Design Supply Air Humidity Ratio Raises: ValueError– if value is not a valid valueReturns: the value of central_cooling_design_supply_air_humidity_ratio or None if not set Return type: float
-
central_cooling_design_supply_air_temperature¶ field Central Cooling Design Supply Air Temperature
Units: CParameters: value (float) – value for IDD Field Central Cooling Design Supply Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of central_cooling_design_supply_air_temperature or None if not set Return type: float
-
central_heating_design_supply_air_humidity_ratio¶ field Central Heating Design Supply Air Humidity Ratio
Units: kgWater/kgDryAirDefault value: 0.008Parameters: value (float) – value for IDD Field Central Heating Design Supply Air Humidity Ratio Raises: ValueError– if value is not a valid valueReturns: the value of central_heating_design_supply_air_humidity_ratio or None if not set Return type: float
-
central_heating_design_supply_air_temperature¶ field Central Heating Design Supply Air Temperature
Units: CParameters: value (float) – value for IDD Field Central Heating Design Supply Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of central_heating_design_supply_air_temperature or None if not set Return type: float
-
central_heating_maximum_system_air_flow_ratio¶ field Central Heating Maximum System Air Flow Ratio
Default value: 0.5value <= 1.0Parameters: value (float) – value for IDD Field Central Heating Maximum System Air Flow Ratio Raises: ValueError– if value is not a valid valueReturns: the value of central_heating_maximum_system_air_flow_ratio or None if not set Return type: float
-
cooling_design_capacity¶ field Cooling Design Capacity
Enter the design cooling capacity.Units: WDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Cooling Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_capacity or None if not set Return type: float or “Autosize”
-
cooling_design_capacity_method¶ field Cooling Design Capacity Method
Enter the method used to determine the system cooling design capacity for scalable sizing.None is used when a cooling coils is not included in an airloop or this field may be blank.If this input field is left blank, then the design cooling capacity is set to zero.CoolingDesignCapacity => selected when the design cooling capacity value is specified orauto-sized. CapacityPerFloorArea => selected when the design cooling capacity is determinedfrom user specified cooling capacity per floor area and total floor area of cooled zonesserved by an airloop. FractionOfAutosizedCoolingCapacity => is selected when the designcooling capacity is determined from a user specified fraction and the auto-sized designcooling capacity of the system.Default value: CoolingDesignCapacityParameters: value (str) – value for IDD Field Cooling Design Capacity Method Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_capacity_method or None if not set Return type: str
-
cooling_design_capacity_per_floor_area¶ field Cooling Design Capacity Per Floor Area
Enter the cooling design capacity per total floor area of cooled zones served by an airloop.Required field when the cooling design capacity method field is CapacityPerFloorArea.Units: W/m2Parameters: value (float) – value for IDD Field Cooling Design Capacity Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_capacity_per_floor_area or None if not set Return type: float
-
cooling_fraction_of_autosized_cooling_supply_air_flow_rate¶ field Cooling Fraction of Autosized Cooling Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate.Required field when Cooling Supply Air Flow Rate Method isFractionOfAutosizedCoolingAirflow.Parameters: value (float) – value for IDD Field Cooling Fraction of Autosized Cooling Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of cooling_fraction_of_autosized_cooling_supply_air_flow_rate or None if not set Return type: float
-
cooling_supply_air_flow_rate¶ field Cooling Supply Air Flow Rate
This input is used if Cooling Supply Air Flow Rate Method is Flow/SystemThis value will not be multiplied by any sizing factor or by zone multipliers.If using zone multipliers, this value must be large enough to serve the multiplied zones.Units: m3/sParameters: value (float) – value for IDD Field Cooling Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate or None if not set Return type: float
-
cooling_supply_air_flow_rate_method¶ field Cooling Supply Air Flow Rate Method
Default value: DesignDayParameters: value (str) – value for IDD Field Cooling Supply Air Flow Rate Method Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate_method or None if not set Return type: str
-
cooling_supply_air_flow_rate_per_floor_area¶ field Cooling Supply Air Flow Rate Per Floor Area
Enter the cooling supply air volume flow rate per total conditioned floor area.Required field when Cooling Supply Air Flow Rate Method is FlowPerFloorArea.Units: m3/s-m2Parameters: value (float) – value for IDD Field Cooling Supply Air Flow Rate Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate_per_floor_area or None if not set Return type: float
-
cooling_supply_air_flow_rate_per_unit_cooling_capacity¶ field Cooling Supply Air Flow Rate Per Unit Cooling Capacity
Enter the supply air volume flow rate per unit cooling capacity.Required field when Cooling Supply Air Flow Rate Method isFlowPerCoolingCapacity.Units: m3/s-WParameters: value (float) – value for IDD Field Cooling Supply Air Flow Rate Per Unit Cooling Capacity Raises: ValueError– if value is not a valid valueReturns: the value of cooling_supply_air_flow_rate_per_unit_cooling_capacity or None if not set Return type: float
-
design_outdoor_air_flow_rate¶ field Design Outdoor Air Flow Rate
Units: m3/sDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Design Outdoor Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of design_outdoor_air_flow_rate or None if not set Return type: float or “Autosize”
-
fraction_of_autosized_cooling_design_capacity¶ field Fraction of Autosized Cooling Design Capacity
Enter the fraction of auto-sized cooling design capacity. Required field when the coolingdesign capacity method field is FractionOfAutosizedCoolingCapacity.Parameters: value (float) – value for IDD Field Fraction of Autosized Cooling Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of fraction_of_autosized_cooling_design_capacity or None if not set Return type: float
-
fraction_of_autosized_heating_design_capacity¶ field Fraction of Autosized Heating Design Capacity
Enter the fraction of auto-sized heating design capacity. Required field when capacity theheating design capacity method field is FractionOfAutosizedHeatingCapacity.Parameters: value (float) – value for IDD Field Fraction of Autosized Heating Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of fraction_of_autosized_heating_design_capacity or None if not set Return type: float
-
heating_design_capacity¶ field Heating Design Capacity
Enter the design heating capacity.Units: WDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Heating Design Capacity Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_capacity or None if not set Return type: float or “Autosize”
-
heating_design_capacity_method¶ field Heating Design Capacity Method
Enter the method used to determine the heating design capacity for scalable sizing.None is used when a heating coil not included in an airloop or this field may be blank.If this input field is left blank, then the design heating capacity is set to zero.HeatingDesignCapacity => selected when the design heating capacity value is specified orauto-sized. CapacityPerFloorArea => selected when the design heating capacity is determinedfrom user specified heating capacity per flow area and total floor area of heated zonesserved by an airloop. FractionOfAutosizedHeatingCapacity => is selected when the designheating capacity is determined from a user specified fraction and the auto-sized designheating capacity of the system.Default value: HeatingDesignCapacityParameters: value (str) – value for IDD Field Heating Design Capacity Method Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_capacity_method or None if not set Return type: str
-
heating_design_capacity_per_floor_area¶ field Heating Design Capacity Per Floor Area
Enter the heating design capacity per zone floor area. Required field when the heating designcapacity method field is CapacityPerFloorArea.Units: W/m2Parameters: value (float) – value for IDD Field Heating Design Capacity Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_capacity_per_floor_area or None if not set Return type: float
-
heating_fraction_of_autosized_cooling_supply_air_flow_rate¶ field Heating Fraction of Autosized Cooling Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate.Required field when Heating Supply Air Flow Rate Method isFractionOfAutosizedCoolingAirflow.Parameters: value (float) – value for IDD Field Heating Fraction of Autosized Cooling Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of heating_fraction_of_autosized_cooling_supply_air_flow_rate or None if not set Return type: float
-
heating_fraction_of_autosized_heating_supply_air_flow_rate¶ field Heating Fraction of Autosized Heating Supply Air Flow Rate
Enter the supply air volume flow rate as a fraction of the heating supply air flow rate.Required field when Heating Supply Air Flow Rate Method isFractionOfAutosizedHeatingAirflow.Parameters: value (float) – value for IDD Field Heating Fraction of Autosized Heating Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of heating_fraction_of_autosized_heating_supply_air_flow_rate or None if not set Return type: float
-
heating_supply_air_flow_rate¶ field Heating Supply Air Flow Rate
Required field when Heating Supply Air Flow Rate Method is Flow/SystemThis value will not be multiplied by any sizing factor or by zone multipliers.If using zone multipliers, this value must be large enough to serve the multiplied zones.Units: m3/sParameters: value (float) – value for IDD Field Heating Supply Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate or None if not set Return type: float
-
heating_supply_air_flow_rate_method¶ field Heating Supply Air Flow Rate Method
Default value: DesignDayParameters: value (str) – value for IDD Field Heating Supply Air Flow Rate Method Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate_method or None if not set Return type: str
-
heating_supply_air_flow_rate_per_floor_area¶ field Heating Supply Air Flow Rate Per Floor Area
Enter the heating supply air volume flow rate per total conditioned floor area.Required field when Heating Supply Air Flow Rate Method is FlowPerFloorArea.Units: m3/s-m2Parameters: value (float) – value for IDD Field Heating Supply Air Flow Rate Per Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate_per_floor_area or None if not set Return type: float
-
heating_supply_air_flow_rate_per_unit_heating_capacity¶ field Heating Supply Air Flow Rate Per Unit Heating Capacity
Enter the heating supply air volume flow rate per unit heating capacity.Required field when Heating Supply Air Flow Rate Method isFlowPerHeatingCapacity.Units: m3/s-WParameters: value (float) – value for IDD Field Heating Supply Air Flow Rate Per Unit Heating Capacity Raises: ValueError– if value is not a valid valueReturns: the value of heating_supply_air_flow_rate_per_unit_heating_capacity or None if not set Return type: float
-
precool_design_humidity_ratio¶ field Precool Design Humidity Ratio
Units: kgWater/kgDryAirParameters: value (float) – value for IDD Field Precool Design Humidity Ratio Raises: ValueError– if value is not a valid valueReturns: the value of precool_design_humidity_ratio or None if not set Return type: float
-
precool_design_temperature¶ field Precool Design Temperature
Units: CParameters: value (float) – value for IDD Field Precool Design Temperature Raises: ValueError– if value is not a valid valueReturns: the value of precool_design_temperature or None if not set Return type: float
-
preheat_design_humidity_ratio¶ field Preheat Design Humidity Ratio
Units: kgWater/kgDryAirParameters: value (float) – value for IDD Field Preheat Design Humidity Ratio Raises: ValueError– if value is not a valid valueReturns: the value of preheat_design_humidity_ratio or None if not set Return type: float
-
preheat_design_temperature¶ field Preheat Design Temperature
Units: CParameters: value (float) – value for IDD Field Preheat Design Temperature Raises: ValueError– if value is not a valid valueReturns: the value of preheat_design_temperature or None if not set Return type: float
-
system_outdoor_air_method¶ field System Outdoor Air Method
Default value: ZoneSumParameters: value (str) – value for IDD Field System Outdoor Air Method Raises: ValueError– if value is not a valid valueReturns: the value of system_outdoor_air_method or None if not set Return type: str
-
type_of_load_to_size_on¶ field Type of Load to Size On
Specifies the basis for sizing the system supply air flow rateSensible and VentilationRequirement are the only available optionsSensible uses the zone design air flow ratesVentilationRequirement uses the system ventilation requirementDefault value: SensibleParameters: value (str) – value for IDD Field Type of Load to Size On Raises: ValueError– if value is not a valid valueReturns: the value of type_of_load_to_size_on or None if not set Return type: str
-
type_of_zone_sum_to_use¶ field Type of Zone Sum to Use
Default value: NonCoincidentParameters: value (str) – value for IDD Field Type of Zone Sum to Use Raises: ValueError– if value is not a valid valueReturns: the value of type_of_zone_sum_to_use or None if not set Return type: str
-
zone_maximum_outdoor_air_fraction¶ field Zone Maximum Outdoor Air Fraction
Units: dimensionlessDefault value: 1.0Parameters: value (float) – value for IDD Field Zone Maximum Outdoor Air Fraction Raises: ValueError– if value is not a valid valueReturns: the value of zone_maximum_outdoor_air_fraction or None if not set Return type: float
-
-
class
pyidf.hvac_design_objects.SizingZone¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object Sizing:Zone Specifies the data needed to perform a zone design air flow calculation. The calculation is done for every sizing period included in the input. The maximum cooling and heating load and cooling, heating, and ventilation air flows are then saved for system level and zone component design calculations.
-
account_for_dedicated_outdoor_air_system¶ field Account for Dedicated Outdoor Air System
account for effect of dedicated outdoor air system supplying air directly to the zoneDefault value: NoParameters: value (str) – value for IDD Field Account for Dedicated Outdoor Air System Raises: ValueError– if value is not a valid valueReturns: the value of account_for_dedicated_outdoor_air_system or None if not set Return type: str
-
cooling_design_air_flow_method¶ field Cooling Design Air Flow Method
Default value: DesignDayParameters: value (str) – value for IDD Field Cooling Design Air Flow Method Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_air_flow_method or None if not set Return type: str
-
cooling_design_air_flow_rate¶ field Cooling Design Air Flow Rate
This input is used if Cooling Design Air Flow Method is Flow/ZoneThis value will be multiplied by the global or zone sizing factor andby zone multipliers.Units: m3/sParameters: value (float) – value for IDD Field Cooling Design Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of cooling_design_air_flow_rate or None if not set Return type: float
-
cooling_minimum_air_flow¶ field Cooling Minimum Air Flow
This input is used if Cooling Design Air Flow Method is DesignDayWithLimitUnits: m3/sParameters: value (float) – value for IDD Field Cooling Minimum Air Flow Raises: ValueError– if value is not a valid valueReturns: the value of cooling_minimum_air_flow or None if not set Return type: float
-
cooling_minimum_air_flow_fraction¶ field Cooling Minimum Air Flow Fraction
fraction of the Cooling design Air Flow RateThis input is currently used in sizing the Fan minimum Flow Rate.It does not currently affect other component autosizing.Parameters: value (float) – value for IDD Field Cooling Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of cooling_minimum_air_flow_fraction or None if not set Return type: float
-
cooling_minimum_air_flow_per_zone_floor_area¶ field Cooling Minimum Air Flow per Zone Floor Area
default is .15 cfm/ft2This input is used if Cooling Design Air Flow Method is DesignDayWithLimitUnits: m3/s-m2Default value: 0.000762Parameters: value (float) – value for IDD Field Cooling Minimum Air Flow per Zone Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of cooling_minimum_air_flow_per_zone_floor_area or None if not set Return type: float
-
dedicated_outdoor_air_high_setpoint_temperature_for_design¶ field Dedicated Outdoor Air High Setpoint Temperature for Design
Units: CDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Dedicated Outdoor Air High Setpoint Temperature for Design Raises: ValueError– if value is not a valid valueReturns: the value of dedicated_outdoor_air_high_setpoint_temperature_for_design or None if not set Return type: float or “Autosize”
-
dedicated_outdoor_air_low_setpoint_temperature_for_design¶ field Dedicated Outdoor Air Low Setpoint Temperature for Design
Units: CDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Dedicated Outdoor Air Low Setpoint Temperature for Design Raises: ValueError– if value is not a valid valueReturns: the value of dedicated_outdoor_air_low_setpoint_temperature_for_design or None if not set Return type: float or “Autosize”
-
dedicated_outdoor_air_system_control_strategy¶ field Dedicated Outdoor Air System Control Strategy
1)supply neutral ventilation air; 2)supply neutral dehumidified and reheatedventilation air; 3)supply cold ventilation airDefault value: NeutralSupplyAirParameters: value (str) – value for IDD Field Dedicated Outdoor Air System Control Strategy Raises: ValueError– if value is not a valid valueReturns: the value of dedicated_outdoor_air_system_control_strategy or None if not set Return type: str
-
design_specification_outdoor_air_object_name¶ field Design Specification Outdoor Air Object Name
Parameters: value (str) – value for IDD Field Design Specification Outdoor Air Object Name Raises: ValueError– if value is not a valid valueReturns: the value of design_specification_outdoor_air_object_name or None if not set Return type: str
-
design_specification_zone_air_distribution_object_name¶ field Design Specification Zone Air Distribution Object Name
Parameters: value (str) – value for IDD Field Design Specification Zone Air Distribution Object Name Raises: ValueError– if value is not a valid valueReturns: the value of design_specification_zone_air_distribution_object_name or None if not set Return type: str
-
heating_design_air_flow_method¶ field Heating Design Air Flow Method
Default value: DesignDayParameters: value (str) – value for IDD Field Heating Design Air Flow Method Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_air_flow_method or None if not set Return type: str
-
heating_design_air_flow_rate¶ field Heating Design Air Flow Rate
This input is used if Heating Design Air Flow Method is Flow/Zone.This value will be multiplied by the global or zone sizing factor andby zone multipliers.Units: m3/sParameters: value (float) – value for IDD Field Heating Design Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of heating_design_air_flow_rate or None if not set Return type: float
-
heating_maximum_air_flow¶ field Heating Maximum Air Flow
default is 300 cfmThis input is used for autosizing components when Heating Design Air Flow Method = DesignDayWithLimit.Units: m3/sDefault value: 0.1415762Parameters: value (float) – value for IDD Field Heating Maximum Air Flow Raises: ValueError– if value is not a valid valueReturns: the value of heating_maximum_air_flow or None if not set Return type: float
-
heating_maximum_air_flow_fraction¶ field Heating Maximum Air Flow Fraction
fraction of the Heating Design Air Flow RateThis input is used for autosizing components when Heating Design Air Flow Method = DesignDayWithLimit.Default value: 0.3Parameters: value (float) – value for IDD Field Heating Maximum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of heating_maximum_air_flow_fraction or None if not set Return type: float
-
heating_maximum_air_flow_per_zone_floor_area¶ field Heating Maximum Air Flow per Zone Floor Area
default is .40 cfm/ft2This field is used to size the heating design flow rate when Heating Design Air Flow Method = Flow/Zone.This input is used for autosizing components when Heating Design Air Flow Method = DesignDayWithLimit.Units: m3/s-m2Default value: 0.002032Parameters: value (float) – value for IDD Field Heating Maximum Air Flow per Zone Floor Area Raises: ValueError– if value is not a valid valueReturns: the value of heating_maximum_air_flow_per_zone_floor_area or None if not set Return type: float
-
zone_cooling_design_supply_air_humidity_ratio¶ field Zone Cooling Design Supply Air Humidity Ratio
Units: kgWater/kgDryAirParameters: value (float) – value for IDD Field Zone Cooling Design Supply Air Humidity Ratio Raises: ValueError– if value is not a valid valueReturns: the value of zone_cooling_design_supply_air_humidity_ratio or None if not set Return type: float
-
zone_cooling_design_supply_air_temperature¶ field Zone Cooling Design Supply Air Temperature
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling DesignSupply Air Temperature Input Method = SupplyAirTemperatureUnits: CParameters: value (float) – value for IDD Field Zone Cooling Design Supply Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of zone_cooling_design_supply_air_temperature or None if not set Return type: float
-
zone_cooling_design_supply_air_temperature_difference¶ field Zone Cooling Design Supply Air Temperature Difference
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling DesignSupply Air Temperature Input Method = TemperatureDifferenceThe absolute value of this field will be subtracted from the zone temperatureat peak load to calculate the Zone Cooling Design Supply Air Temperature.Units: deltaCParameters: value (float) – value for IDD Field Zone Cooling Design Supply Air Temperature Difference Raises: ValueError– if value is not a valid valueReturns: the value of zone_cooling_design_supply_air_temperature_difference or None if not set Return type: float
-
zone_cooling_design_supply_air_temperature_input_method¶ field Zone Cooling Design Supply Air Temperature Input Method
Default value: SupplyAirTemperatureParameters: value (str) – value for IDD Field Zone Cooling Design Supply Air Temperature Input Method Raises: ValueError– if value is not a valid valueReturns: the value of zone_cooling_design_supply_air_temperature_input_method or None if not set Return type: str
-
zone_cooling_sizing_factor¶ field Zone Cooling Sizing Factor
if blank or zero, global cooling sizing factor from Sizing:Parameters is used.Parameters: value (float) – value for IDD Field Zone Cooling Sizing Factor Raises: ValueError– if value is not a valid valueReturns: the value of zone_cooling_sizing_factor or None if not set Return type: float
-
zone_heating_design_supply_air_humidity_ratio¶ field Zone Heating Design Supply Air Humidity Ratio
Units: kgWater/kgDryAirParameters: value (float) – value for IDD Field Zone Heating Design Supply Air Humidity Ratio Raises: ValueError– if value is not a valid valueReturns: the value of zone_heating_design_supply_air_humidity_ratio or None if not set Return type: float
-
zone_heating_design_supply_air_temperature¶ field Zone Heating Design Supply Air Temperature
Zone Heating Design Supply Air Temperature is only used when Zone Heating DesignSupply Air Temperature Input Method = SupplyAirTemperatureUnits: CParameters: value (float) – value for IDD Field Zone Heating Design Supply Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of zone_heating_design_supply_air_temperature or None if not set Return type: float
-
zone_heating_design_supply_air_temperature_difference¶ field Zone Heating Design Supply Air Temperature Difference
Zone Heating Design Supply Air Temperature is only used when Zone Heating DesignSupply Air Temperature Input Method = TemperatureDifferenceThe absolute value of this field will be added to the zone temperatureat peak load to calculate the Zone Heating Design Supply Air Temperature.Units: deltaCParameters: value (float) – value for IDD Field Zone Heating Design Supply Air Temperature Difference Raises: ValueError– if value is not a valid valueReturns: the value of zone_heating_design_supply_air_temperature_difference or None if not set Return type: float
-
zone_heating_design_supply_air_temperature_input_method¶ field Zone Heating Design Supply Air Temperature Input Method
Default value: SupplyAirTemperatureParameters: value (str) – value for IDD Field Zone Heating Design Supply Air Temperature Input Method Raises: ValueError– if value is not a valid valueReturns: the value of zone_heating_design_supply_air_temperature_input_method or None if not set Return type: str
-
zone_heating_sizing_factor¶ field Zone Heating Sizing Factor
if blank or zero, global heating sizing factor from Sizing:Parameters is used.Parameters: value (float) – value for IDD Field Zone Heating Sizing Factor Raises: ValueError– if value is not a valid valueReturns: the value of zone_heating_sizing_factor or None if not set Return type: float
-
zone_or_zonelist_name¶ field Zone or ZoneList Name
Parameters: value (str) – value for IDD Field Zone or ZoneList Name Raises: ValueError– if value is not a valid valueReturns: the value of zone_or_zonelist_name or None if not set Return type: str
-