pyidf.zone_hvac_air_loop_terminal_units module¶
Data objects in group “Zone HVAC Air Loop Terminal Units”
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalDualDuctConstantVolume¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:DualDuct:ConstantVolume Central air system terminal unit, dual duct, constant volume.
-
air_outlet_node_name¶ field Air Outlet Node Name
The outlet node of the terminal unit.This is also the zone inlet node.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
cold_air_inlet_node_name¶ field Cold Air Inlet Node Name
Parameters: value (str) – value for IDD Field Cold Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of cold_air_inlet_node_name or None if not set Return type: str
-
hot_air_inlet_node_name¶ field Hot Air Inlet Node Name
Parameters: value (str) – value for IDD Field Hot Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_air_inlet_node_name or None if not set Return type: str
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalDualDuctVav¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:DualDuct:VAV Central air system terminal unit, dual duct, variable volume.
-
air_outlet_node_name¶ field Air Outlet Node Name
The outlet node of the terminal unit.This is also the zone inlet node.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
cold_air_inlet_node_name¶ field Cold Air Inlet Node Name
Parameters: value (str) – value for IDD Field Cold Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of cold_air_inlet_node_name or None if not set Return type: str
-
design_specification_outdoor_air_object_name¶ field Design Specification Outdoor Air Object Name
When the name of a DesignSpecification:OutdoorAir object is entered, the terminalunit will increase flow as needed to meet this outdoor air requirement.If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement willbe computed based on the current number of occupants in the zone.At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate.If this field is blank, then the terminal unit will not be controlled for outdoor air flow.Parameters: value (str) – value for IDD Field Design Specification Outdoor Air Object Name Raises: ValueError– if value is not a valid valueReturns: the value of design_specification_outdoor_air_object_name or None if not set Return type: str
-
hot_air_inlet_node_name¶ field Hot Air Inlet Node Name
Parameters: value (str) – value for IDD Field Hot Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_air_inlet_node_name or None if not set Return type: str
-
maximum_damper_air_flow_rate¶ field Maximum Damper Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Damper Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_damper_air_flow_rate or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
zone_minimum_air_flow_fraction¶ field Zone Minimum Air Flow Fraction
fraction of maximum air flowDefault value: 0.2value <= 1.0Parameters: value (float) – value for IDD Field Zone Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of zone_minimum_air_flow_fraction or None if not set Return type: float
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalDualDuctVavOutdoorAir¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:DualDuct:VAV:OutdoorAir Central air system terminal unit, dual duct, variable volume with special controls. One VAV duct is controlled to supply ventilation air and the other VAV duct is controlled to meet the zone cooling load.
-
air_outlet_node_name¶ field Air Outlet Node Name
The outlet node of the terminal unit.This is also the zone inlet node.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
design_specification_outdoor_air_object_name¶ field Design Specification Outdoor Air Object Name
When the name of a DesignSpecification:OutdoorAir object is entered, the terminalunit will increase flow as needed to meet this outdoor air requirement.If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement willbe computed based mode selected in the next field.At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate.Parameters: value (str) – value for IDD Field Design Specification Outdoor Air Object Name Raises: ValueError– if value is not a valid valueReturns: the value of design_specification_outdoor_air_object_name or None if not set Return type: str
-
maximum_terminal_air_flow_rate¶ field Maximum Terminal Air Flow Rate
If autosized this is the sum of flow needed for cooling and maximum required outdoor airUnits: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Terminal Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_terminal_air_flow_rate or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
outdoor_air_inlet_node_name¶ field Outdoor Air Inlet Node Name
Parameters: value (str) – value for IDD Field Outdoor Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of outdoor_air_inlet_node_name or None if not set Return type: str
-
per_person_ventilation_rate_mode¶ field Per Person Ventilation Rate Mode
CurrentOccupancy models demand controlled ventilation using the current number of peopleDesignOccupancy uses the total Number of People in the zone and is constantParameters: value (str) – value for IDD Field Per Person Ventilation Rate Mode Raises: ValueError– if value is not a valid valueReturns: the value of per_person_ventilation_rate_mode or None if not set Return type: str
-
recirculated_air_inlet_node_name¶ field Recirculated Air Inlet Node Name
Parameters: value (str) – value for IDD Field Recirculated Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of recirculated_air_inlet_node_name or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctConstantVolumeCooledBeam¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:ConstantVolume:CooledBeam Central air system terminal unit, single duct, constant volume, with cooled beam (active or passive).
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
beam_length¶ field Beam Length
Length of an individual beam unitUnits: mDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of beam_length or None if not set Return type: float or “Autosize”
-
chilled_water_inlet_node_name¶ field Chilled Water Inlet Node Name
Parameters: value (str) – value for IDD Field Chilled Water Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of chilled_water_inlet_node_name or None if not set Return type: str
-
chilled_water_outlet_node_name¶ field Chilled Water Outlet Node Name
Parameters: value (str) – value for IDD Field Chilled Water Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of chilled_water_outlet_node_name or None if not set Return type: str
-
coefficient_of_induction_kin¶ field Coefficient of Induction Kin
Default value: “Autocalculate”value <= 4.0Parameters: value (float or “Autocalculate”) – value for IDD Field Coefficient of Induction Kin Raises: ValueError– if value is not a valid valueReturns: the value of coefficient_of_induction_kin or None if not set Return type: float or “Autocalculate”
-
coil_surface_area_per_coil_length¶ field Coil Surface Area per Coil Length
Units: m2/mDefault value: 5.422Parameters: value (float) – value for IDD Field Coil Surface Area per Coil Length Raises: ValueError– if value is not a valid valueReturns: the value of coil_surface_area_per_coil_length or None if not set Return type: float
-
cooled_beam_type¶ field Cooled Beam Type
Parameters: value (str) – value for IDD Field Cooled Beam Type Raises: ValueError– if value is not a valid valueReturns: the value of cooled_beam_type or None if not set Return type: str
-
design_inlet_water_temperature¶ field Design Inlet Water Temperature
Units: CDefault value: 15.0Parameters: value (float) – value for IDD Field Design Inlet Water Temperature Raises: ValueError– if value is not a valid valueReturns: the value of design_inlet_water_temperature or None if not set Return type: float
-
design_outlet_water_temperature¶ field Design Outlet Water Temperature
Units: CDefault value: 17.0Parameters: value (float) – value for IDD Field Design Outlet Water Temperature Raises: ValueError– if value is not a valid valueReturns: the value of design_outlet_water_temperature or None if not set Return type: float
-
leaving_pipe_inside_diameter¶ field Leaving Pipe Inside Diameter
Units: mDefault value: 0.0145Parameters: value (float) – value for IDD Field Leaving Pipe Inside Diameter Raises: ValueError– if value is not a valid valueReturns: the value of leaving_pipe_inside_diameter or None if not set Return type: float
-
maximum_total_chilled_water_volumetric_flow_rate¶ field Maximum Total Chilled Water Volumetric Flow Rate
Units: m3/sDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Maximum Total Chilled Water Volumetric Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_total_chilled_water_volumetric_flow_rate or None if not set Return type: float or “Autosize”
-
model_parameter_a¶ field Model Parameter a
Default value: 15.3Parameters: value (float) – value for IDD Field Model Parameter a Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_a or None if not set Return type: float
-
model_parameter_a0¶ field Model Parameter a0
Free area of the coil in plan view per unit beam lengthUnits: m2/mDefault value: 0.171Parameters: value (float) – value for IDD Field Model Parameter a0 Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_a0 or None if not set Return type: float
-
model_parameter_k1¶ field Model Parameter K1
Default value: 0.0057Parameters: value (float) – value for IDD Field Model Parameter K1 Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_k1 or None if not set Return type: float
-
model_parameter_n¶ field Model Parameter n
Default value: 0.4Parameters: value (float) – value for IDD Field Model Parameter n Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_n or None if not set Return type: float
-
model_parameter_n1¶ field Model Parameter n1
Parameters: value (float) – value for IDD Field Model Parameter n1 Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_n1 or None if not set Return type: float
-
model_parameter_n2¶ field Model Parameter n2
Default value: 0.84Parameters: value (float) – value for IDD Field Model Parameter n2 Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_n2 or None if not set Return type: float
-
model_parameter_n3¶ field Model Parameter n3
Default value: 0.12Parameters: value (float) – value for IDD Field Model Parameter n3 Raises: ValueError– if value is not a valid valueReturns: the value of model_parameter_n3 or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
number_of_beams¶ field Number of Beams
Number of individual beam units in the zoneDefault value: “autosize”Parameters: value (int or “Autosize”) – value for IDD Field Number of Beams Raises: ValueError– if value is not a valid valueReturns: the value of number_of_beams or None if not set Return type: int or “Autosize”
-
supply_air_inlet_node_name¶ field Supply Air Inlet Node Name
Parameters: value (str) – value for IDD Field Supply Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of supply_air_inlet_node_name or None if not set Return type: str
-
supply_air_outlet_node_name¶ field Supply Air Outlet Node Name
Parameters: value (str) – value for IDD Field Supply Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of supply_air_outlet_node_name or None if not set Return type: str
-
supply_air_volumetric_flow_rate¶ field Supply Air Volumetric Flow Rate
Units: m3/sDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Supply Air Volumetric Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of supply_air_volumetric_flow_rate or None if not set Return type: float or “Autosize”
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctConstantVolumeFourPipeBeam¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:ConstantVolume:FourPipeBeam Central air system terminal unit, single duct, constant volume, with heating and/or cooling. Operates as two-pipe unit if heating or cooling water is omitted. Heating and/or cooling can be scheduled off for dedicated ventilation.
-
beam_cooling_capacity_air_flow_modification_factor_curve_name¶ field Beam Cooling Capacity Air Flow Modification Factor Curve Name
Adjusts beam cooling capacity when the primary air supply flow rate is differentthan at the rating point. The single independent variable is the current normalizedair flow rate divided by the normalized air flow rate at the rating point.This field is required when beam is connected to a chilled water plant.Parameters: value (str) – value for IDD Field Beam Cooling Capacity Air Flow Modification Factor Curve Name Raises: ValueError– if value is not a valid valueReturns: the value of beam_cooling_capacity_air_flow_modification_factor_curve_name or None if not set Return type: str
-
beam_cooling_capacity_chilled_water_flow_modification_factor_curve_name¶ field Beam Cooling Capacity Chilled Water Flow Modification Factor Curve Name
Adjusts beam cooling capacity when the normalized chilled water flow rate is differentthan at the rating point. The single independent variable is the current normalizedchilled water flow rate divided by the normalized chilled water flow rate at the rating point.This field is required when beam is connected to a chilled water plant.Parameters: value (str) – value for IDD Field Beam Cooling Capacity Chilled Water Flow Modification Factor Curve Name Raises: ValueError– if value is not a valid valueReturns: the value of beam_cooling_capacity_chilled_water_flow_modification_factor_curve_name or None if not set Return type: str
-
beam_cooling_capacity_temperature_difference_modification_factor_curve_name¶ field Beam Cooling Capacity Temperature Difference Modification Factor Curve Name
Adjusts beam cooling capacity when the temperature difference between entering water and zone airis different than at the rating point. Single independent variable is the ratio of the currenttemperature difference divided by the rating point temperature difference.This field is required when beam is connected to a chilled water plant.Parameters: value (str) – value for IDD Field Beam Cooling Capacity Temperature Difference Modification Factor Curve Name Raises: ValueError– if value is not a valid valueReturns: the value of beam_cooling_capacity_temperature_difference_modification_factor_curve_name or None if not set Return type: str
-
beam_heating_capacity_air_flow_modification_factor_curve_name¶ field Beam Heating Capacity Air Flow Modification Factor Curve Name
Adjusts beam heating capacity when the primary air supply flow rate is differentthan at the rating point. The single independent variable is the current normalizedair flow rate divided by the normalized air flow rate at the rating point.This field is required when beam is connected to a hot water plant.Parameters: value (str) – value for IDD Field Beam Heating Capacity Air Flow Modification Factor Curve Name Raises: ValueError– if value is not a valid valueReturns: the value of beam_heating_capacity_air_flow_modification_factor_curve_name or None if not set Return type: str
-
beam_heating_capacity_hot_water_flow_modification_factor_curve_name¶ field Beam Heating Capacity Hot Water Flow Modification Factor Curve Name
Adjusts beam heating capacity when the normalized hot water flow rate is differentthan at the rating point. The single independent variable is the current normalizedhot water flow rate divided by the normalized hot water flow rate at the rating point.This field is required when beam is connected to a hot water plant.Parameters: value (str) – value for IDD Field Beam Heating Capacity Hot Water Flow Modification Factor Curve Name Raises: ValueError– if value is not a valid valueReturns: the value of beam_heating_capacity_hot_water_flow_modification_factor_curve_name or None if not set Return type: str
-
beam_heating_capacity_temperature_difference_modification_factor_curve_name¶ field Beam Heating Capacity Temperature Difference Modification Factor Curve Name
Adjusts beam heating capacity when the temperature difference between entering water and zone airis different than at the rating point. Single independent variable is the ratio of the currenttemperature difference divided by the rating point temperature difference.This field is required when beam is connected to a hot water plant.Parameters: value (str) – value for IDD Field Beam Heating Capacity Temperature Difference Modification Factor Curve Name Raises: ValueError– if value is not a valid valueReturns: the value of beam_heating_capacity_temperature_difference_modification_factor_curve_name or None if not set Return type: str
-
beam_rated_chilled_water_volume_flow_rate_per_beam_length¶ field Beam Rated Chilled Water Volume Flow Rate per Beam Length
The volume flow rate of chilled water per meter of beam length at the rating point.Units: m3/s-mDefault value: 5e-05Parameters: value (float) – value for IDD Field Beam Rated Chilled Water Volume Flow Rate per Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of beam_rated_chilled_water_volume_flow_rate_per_beam_length or None if not set Return type: float
-
beam_rated_cooling_capacity_per_beam_length¶ field Beam Rated Cooling Capacity per Beam Length
Sensible cooling capacity per meter of beam length at the rating point.Units: W/mDefault value: 600.0Parameters: value (float) – value for IDD Field Beam Rated Cooling Capacity per Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of beam_rated_cooling_capacity_per_beam_length or None if not set Return type: float
-
beam_rated_cooling_room_air_chilled_water_temperature_difference¶ field Beam Rated Cooling Room Air Chilled Water Temperature Difference
Difference in temperature between the zone air and the entering chilled water at the rating point.Units: deltaCDefault value: 10.0Parameters: value (float) – value for IDD Field Beam Rated Cooling Room Air Chilled Water Temperature Difference Raises: ValueError– if value is not a valid valueReturns: the value of beam_rated_cooling_room_air_chilled_water_temperature_difference or None if not set Return type: float
-
beam_rated_heating_capacity_per_beam_length¶ field Beam Rated Heating Capacity per Beam Length
Sensible heating capacity per meter of beam length at the rating point.Units: W/mDefault value: 1500.0Parameters: value (float) – value for IDD Field Beam Rated Heating Capacity per Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of beam_rated_heating_capacity_per_beam_length or None if not set Return type: float
-
beam_rated_heating_room_air_hot_water_temperature_difference¶ field Beam Rated Heating Room Air Hot Water Temperature Difference
Difference in temperature between the zone air and the entering hot water at the rating point.Units: deltaCDefault value: 27.8Parameters: value (float) – value for IDD Field Beam Rated Heating Room Air Hot Water Temperature Difference Raises: ValueError– if value is not a valid valueReturns: the value of beam_rated_heating_room_air_hot_water_temperature_difference or None if not set Return type: float
-
beam_rated_hot_water_volume_flow_rate_per_beam_length¶ field Beam Rated Hot Water Volume Flow Rate per Beam Length
The volume flow rate of hoy water per meter of beam length at the rating point.Units: m3/s-mDefault value: 5e-05Parameters: value (float) – value for IDD Field Beam Rated Hot Water Volume Flow Rate per Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of beam_rated_hot_water_volume_flow_rate_per_beam_length or None if not set Return type: float
-
chilled_water_inlet_node_name¶ field Chilled Water Inlet Node Name
Name of the plant system node for chilled water entering the beam.The two chilled water nodes can (only) be omitted to model a two-pipe heating only beam.Parameters: value (str) – value for IDD Field Chilled Water Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of chilled_water_inlet_node_name or None if not set Return type: str
-
chilled_water_outlet_node_name¶ field Chilled Water Outlet Node Name
Name of the plant system node for chilled water leaving the beam.Parameters: value (str) – value for IDD Field Chilled Water Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of chilled_water_outlet_node_name or None if not set Return type: str
-
cooling_availability_schedule_name¶ field Cooling Availability Schedule Name
Cooling operation can be controlled separately using this availability schedule.Schedule value > 0 means beam cooling is available.If this field is blank, the beam cooling is always available (as long as primary air is also available).Parameters: value (str) – value for IDD Field Cooling Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of cooling_availability_schedule_name or None if not set Return type: str
-
design_chilled_water_volume_flow_rate¶ field Design Chilled Water Volume Flow Rate
Units: m3/sDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Design Chilled Water Volume Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of design_chilled_water_volume_flow_rate or None if not set Return type: float or “Autosize”
-
design_hot_water_volume_flow_rate¶ field Design Hot Water Volume Flow Rate
Units: m3/sDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Design Hot Water Volume Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of design_hot_water_volume_flow_rate or None if not set Return type: float or “Autosize”
-
design_primary_air_volume_flow_rate¶ field Design Primary Air Volume Flow Rate
Units: m3/sDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Design Primary Air Volume Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of design_primary_air_volume_flow_rate or None if not set Return type: float or “Autosize”
-
heating_availability_schedule_name¶ field Heating Availability Schedule Name
Heating operation can be controlled separately using this availability schedule.Schedule value > 0 means beam heating is available.If this field is blank, the beam heating is always available (as long as primary air is also available).Parameters: value (str) – value for IDD Field Heating Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of heating_availability_schedule_name or None if not set Return type: str
-
hot_water_inlet_node_name¶ field Hot Water Inlet Node Name
Name of the plant system node for hot water entering the beam.The two hot water nodes can (only) be omitted to model a two-pipe cooling-only beam.Parameters: value (str) – value for IDD Field Hot Water Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_inlet_node_name or None if not set Return type: str
-
hot_water_outlet_node_name¶ field Hot Water Outlet Node Name
Name of the plant system node for hot water leaving the beam.Parameters: value (str) – value for IDD Field Hot Water Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_outlet_node_name or None if not set Return type: str
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
primary_air_availability_schedule_name¶ field Primary Air Availability Schedule Name
Primary air is supplied by central air handling unit and must be on for heating or cooling.Schedule value > 0 means the primary air supply is available.If this field is blank, the primary air supply is always available.Parameters: value (str) – value for IDD Field Primary Air Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of primary_air_availability_schedule_name or None if not set Return type: str
-
primary_air_inlet_node_name¶ field Primary Air Inlet Node Name
Name of the air system node for primary supply air entering the air distribution unit.Parameters: value (str) – value for IDD Field Primary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of primary_air_inlet_node_name or None if not set Return type: str
-
primary_air_outlet_node_name¶ field Primary Air Outlet Node Name
Name of the air system node for primary supply air leaving the air distribution unit and entering the zone.Parameters: value (str) – value for IDD Field Primary Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of primary_air_outlet_node_name or None if not set Return type: str
-
rated_primary_air_flow_rate_per_beam_length¶ field Rated Primary Air Flow Rate per Beam Length
Primary air supply flow rate normalized by beam length.Units: m3/s-mDefault value: 0.035Parameters: value (float) – value for IDD Field Rated Primary Air Flow Rate per Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of rated_primary_air_flow_rate_per_beam_length or None if not set Return type: float
-
zone_total_beam_length¶ field Zone Total Beam Length
Sum of the length of all the beam units in the zone represented by this terminal unit.Units: mDefault value: “autosize”Parameters: value (float or “Autosize”) – value for IDD Field Zone Total Beam Length Raises: ValueError– if value is not a valid valueReturns: the value of zone_total_beam_length or None if not set Return type: float or “Autosize”
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctConstantVolumeFourPipeInduction¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction Central air system terminal unit, single duct, variable volume, induction unit with hot water reheat coil and chilled water recool coil.
-
air_outlet_node_name¶ field Air Outlet Node Name
should be a zone inlet nodeParameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
cold_water_inlet_node_name¶ field Cold Water Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Cold Water Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of cold_water_inlet_node_name or None if not set Return type: str
-
cooling_coil_name¶ field Cooling Coil Name
Parameters: value (str) – value for IDD Field Cooling Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of cooling_coil_name or None if not set Return type: str
-
cooling_coil_object_type¶ field Cooling Coil Object Type
Parameters: value (str) – value for IDD Field Cooling Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of cooling_coil_object_type or None if not set Return type: str
-
cooling_convergence_tolerance¶ field Cooling Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Cooling Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of cooling_convergence_tolerance or None if not set Return type: float
-
heating_coil_name¶ field Heating Coil Name
Parameters: value (str) – value for IDD Field Heating Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of heating_coil_name or None if not set Return type: str
-
heating_coil_object_type¶ field Heating Coil Object Type
Parameters: value (str) – value for IDD Field Heating Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of heating_coil_object_type or None if not set Return type: str
-
heating_convergence_tolerance¶ field Heating Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Heating Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of heating_convergence_tolerance or None if not set Return type: float
-
hot_water_inlet_node_name¶ field Hot Water Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Hot Water Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_inlet_node_name or None if not set Return type: str
-
induced_air_inlet_node_name¶ field Induced Air Inlet Node Name
should be a zone exhaust node, also the heating coil inlet nodeParameters: value (str) – value for IDD Field Induced Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of induced_air_inlet_node_name or None if not set Return type: str
-
induction_ratio¶ field Induction Ratio
ratio of induced air flow rate to primary air flow rateDefault value: 2.5Parameters: value (float) – value for IDD Field Induction Ratio Raises: ValueError– if value is not a valid valueReturns: the value of induction_ratio or None if not set Return type: float
-
maximum_cold_water_flow_rate¶ field Maximum Cold Water Flow Rate
Units: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Cold Water Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_cold_water_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_hot_water_flow_rate¶ field Maximum Hot Water Flow Rate
Not used when heating coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_total_air_flow_rate¶ field Maximum Total Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Total Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_total_air_flow_rate or None if not set Return type: float or “Autosize”
-
minimum_cold_water_flow_rate¶ field Minimum Cold Water Flow Rate
Units: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Cold Water Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_cold_water_flow_rate or None if not set Return type: float
-
minimum_hot_water_flow_rate¶ field Minimum Hot Water Flow Rate
Not used when heating coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_flow_rate or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
supply_air_inlet_node_name¶ field Supply Air Inlet Node Name
Parameters: value (str) – value for IDD Field Supply Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of supply_air_inlet_node_name or None if not set Return type: str
-
zone_mixer_name¶ field Zone Mixer Name
Parameters: value (str) – value for IDD Field Zone Mixer Name Raises: ValueError– if value is not a valid valueReturns: the value of zone_mixer_name or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctConstantVolumeReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:ConstantVolume:Reheat Central air system terminal unit, single duct, constant volume, with reheat coil (hot water, electric, gas, or steam).
-
air_inlet_node_name¶ field Air Inlet Node Name
Parameters: value (str) – value for IDD Field Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_inlet_node_name or None if not set Return type: str
-
air_outlet_node_name¶ field Air Outlet Node Name
Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
convergence_tolerance¶ field Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of convergence_tolerance or None if not set Return type: float
-
hot_water_or_steam_inlet_node_name¶ field Hot Water or Steam Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Hot Water or Steam Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_or_steam_inlet_node_name or None if not set Return type: str
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_hot_water_or_steam_flow_rate¶ field Maximum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_or_steam_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_reheat_air_temperature¶ field Maximum Reheat Air Temperature
Specifies the maximum allowable supply air temperature leaving the reheat coil.If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.Units: CParameters: value (float) – value for IDD Field Maximum Reheat Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of maximum_reheat_air_temperature or None if not set Return type: float
-
minimum_hot_water_or_steam_flow_rate¶ field Minimum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_or_steam_flow_rate or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
reheat_coil_name¶ field Reheat Coil Name
Parameters: value (str) – value for IDD Field Reheat Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_name or None if not set Return type: str
-
reheat_coil_object_type¶ field Reheat Coil Object Type
Parameters: value (str) – value for IDD Field Reheat Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_object_type or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctInletSideMixer¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:InletSideMixer The inlet side mixer air terminal unit provides a means of supplying central system air to the air inlet of a zone AC unit such as a four pipe fan coil. Normally the central air would be ventilation air from a dedicated outdoor air system (DOAS).
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
terminal_unit_outlet_node_name¶ field Terminal Unit Outlet Node Name
Parameters: value (str) – value for IDD Field Terminal Unit Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of terminal_unit_outlet_node_name or None if not set Return type: str
-
terminal_unit_primary_air_inlet_node_name¶ field Terminal Unit Primary Air Inlet Node Name
Parameters: value (str) – value for IDD Field Terminal Unit Primary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of terminal_unit_primary_air_inlet_node_name or None if not set Return type: str
-
terminal_unit_secondary_air_inlet_node_name¶ field Terminal Unit Secondary Air Inlet Node Name
Parameters: value (str) – value for IDD Field Terminal Unit Secondary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of terminal_unit_secondary_air_inlet_node_name or None if not set Return type: str
-
zonehvac_terminal_unit_name¶ field ZoneHVAC Terminal Unit Name
Parameters: value (str) – value for IDD Field ZoneHVAC Terminal Unit Name Raises: ValueError– if value is not a valid valueReturns: the value of zonehvac_terminal_unit_name or None if not set Return type: str
-
zonehvac_terminal_unit_object_type¶ field ZoneHVAC Terminal Unit Object Type
Parameters: value (str) – value for IDD Field ZoneHVAC Terminal Unit Object Type Raises: ValueError– if value is not a valid valueReturns: the value of zonehvac_terminal_unit_object_type or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctParallelPiuReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:ParallelPIU:Reheat Central air system terminal unit, single duct, variable volume, parallel powered induction unit (PIU), with reheat coil (hot water, electric, gas, or steam).
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
convergence_tolerance¶ field Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of convergence_tolerance or None if not set Return type: float
-
fan_name¶ field Fan Name
Fan type must be Fan:ConstantVolumeParameters: value (str) – value for IDD Field Fan Name Raises: ValueError– if value is not a valid valueReturns: the value of fan_name or None if not set Return type: str
-
fan_on_flow_fraction¶ field Fan On Flow Fraction
the fraction of the primary air flow at which fan turns onvalue <= 1.0Parameters: value (float or “Autosize”) – value for IDD Field Fan On Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of fan_on_flow_fraction or None if not set Return type: float or “Autosize”
-
hot_water_or_steam_inlet_node_name¶ field Hot Water or Steam Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Hot Water or Steam Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_or_steam_inlet_node_name or None if not set Return type: str
-
maximum_hot_water_or_steam_flow_rate¶ field Maximum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_or_steam_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_primary_air_flow_rate¶ field Maximum Primary Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Primary Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_primary_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_secondary_air_flow_rate¶ field Maximum Secondary Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Secondary Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_secondary_air_flow_rate or None if not set Return type: float or “Autosize”
-
minimum_hot_water_or_steam_flow_rate¶ field Minimum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_or_steam_flow_rate or None if not set Return type: float
-
minimum_primary_air_flow_fraction¶ field Minimum Primary Air Flow Fraction
value <= 1.0Parameters: value (float or “Autosize”) – value for IDD Field Minimum Primary Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of minimum_primary_air_flow_fraction or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
outlet_node_name¶ field Outlet Node Name
Parameters: value (str) – value for IDD Field Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of outlet_node_name or None if not set Return type: str
-
reheat_coil_air_inlet_node_name¶ field Reheat Coil Air Inlet Node Name
mixer outlet nodeParameters: value (str) – value for IDD Field Reheat Coil Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_air_inlet_node_name or None if not set Return type: str
-
reheat_coil_name¶ field Reheat Coil Name
Parameters: value (str) – value for IDD Field Reheat Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_name or None if not set Return type: str
-
reheat_coil_object_type¶ field Reheat Coil Object Type
Parameters: value (str) – value for IDD Field Reheat Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_object_type or None if not set Return type: str
-
secondary_air_inlet_node_name¶ field Secondary Air Inlet Node Name
Parameters: value (str) – value for IDD Field Secondary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of secondary_air_inlet_node_name or None if not set Return type: str
-
supply_air_inlet_node_name¶ field Supply Air Inlet Node Name
Parameters: value (str) – value for IDD Field Supply Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of supply_air_inlet_node_name or None if not set Return type: str
-
zone_mixer_name¶ field Zone Mixer Name
Parameters: value (str) – value for IDD Field Zone Mixer Name Raises: ValueError– if value is not a valid valueReturns: the value of zone_mixer_name or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctSeriesPiuReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:SeriesPIU:Reheat Central air system terminal unit, single duct, variable volume, series powered induction unit (PIU), with reheat coil (hot water, electric, gas, or steam).
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
convergence_tolerance¶ field Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of convergence_tolerance or None if not set Return type: float
-
fan_name¶ field Fan Name
Fan type must be Fan:ConstantVolumeParameters: value (str) – value for IDD Field Fan Name Raises: ValueError– if value is not a valid valueReturns: the value of fan_name or None if not set Return type: str
-
hot_water_or_steam_inlet_node_name¶ field Hot Water or Steam Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Hot Water or Steam Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_or_steam_inlet_node_name or None if not set Return type: str
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_hot_water_or_steam_flow_rate¶ field Maximum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_or_steam_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_primary_air_flow_rate¶ field Maximum Primary Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Primary Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_primary_air_flow_rate or None if not set Return type: float or “Autosize”
-
minimum_hot_water_or_steam_flow_rate¶ field Minimum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_or_steam_flow_rate or None if not set Return type: float
-
minimum_primary_air_flow_fraction¶ field Minimum Primary Air Flow Fraction
value <= 1.0Parameters: value (float or “Autosize”) – value for IDD Field Minimum Primary Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of minimum_primary_air_flow_fraction or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
outlet_node_name¶ field Outlet Node Name
Parameters: value (str) – value for IDD Field Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of outlet_node_name or None if not set Return type: str
-
reheat_coil_air_inlet_node_name¶ field Reheat Coil Air Inlet Node Name
Parameters: value (str) – value for IDD Field Reheat Coil Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_air_inlet_node_name or None if not set Return type: str
-
reheat_coil_name¶ field Reheat Coil Name
Parameters: value (str) – value for IDD Field Reheat Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_name or None if not set Return type: str
-
reheat_coil_object_type¶ field Reheat Coil Object Type
Parameters: value (str) – value for IDD Field Reheat Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_object_type or None if not set Return type: str
-
secondary_air_inlet_node_name¶ field Secondary Air Inlet Node Name
Parameters: value (str) – value for IDD Field Secondary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of secondary_air_inlet_node_name or None if not set Return type: str
-
supply_air_inlet_node_name¶ field Supply Air Inlet Node Name
Parameters: value (str) – value for IDD Field Supply Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of supply_air_inlet_node_name or None if not set Return type: str
-
zone_mixer_name¶ field Zone Mixer Name
Parameters: value (str) – value for IDD Field Zone Mixer Name Raises: ValueError– if value is not a valid valueReturns: the value of zone_mixer_name or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctSupplySideMixer¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:SupplySideMixer The supply side mixer air terminal unit provides a means of supplying central system air to the air outlet of a zone AC unit such as a four pipe fan coil. Normally the central air would be ventilation air from a dedicated outdoor air system (DOAS).
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
terminal_unit_outlet_node_name¶ field Terminal Unit Outlet Node Name
Parameters: value (str) – value for IDD Field Terminal Unit Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of terminal_unit_outlet_node_name or None if not set Return type: str
-
terminal_unit_primary_air_inlet_node_name¶ field Terminal Unit Primary Air Inlet Node Name
Parameters: value (str) – value for IDD Field Terminal Unit Primary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of terminal_unit_primary_air_inlet_node_name or None if not set Return type: str
-
terminal_unit_secondary_air_inlet_node_name¶ field Terminal Unit Secondary Air Inlet Node Name
Parameters: value (str) – value for IDD Field Terminal Unit Secondary Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of terminal_unit_secondary_air_inlet_node_name or None if not set Return type: str
-
zonehvac_terminal_unit_name¶ field ZoneHVAC Terminal Unit Name
Parameters: value (str) – value for IDD Field ZoneHVAC Terminal Unit Name Raises: ValueError– if value is not a valid valueReturns: the value of zonehvac_terminal_unit_name or None if not set Return type: str
-
zonehvac_terminal_unit_object_type¶ field ZoneHVAC Terminal Unit Object Type
Parameters: value (str) – value for IDD Field ZoneHVAC Terminal Unit Object Type Raises: ValueError– if value is not a valid valueReturns: the value of zonehvac_terminal_unit_object_type or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctUncontrolled¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:Uncontrolled Central air system terminal unit, single duct, constant volume, no controls other than on/off schedule.
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
zone_supply_air_node_name¶ field Zone Supply Air Node Name
Parameters: value (str) – value for IDD Field Zone Supply Air Node Name Raises: ValueError– if value is not a valid valueReturns: the value of zone_supply_air_node_name or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctVavHeatAndCoolNoReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat Central air system terminal unit, single duct, variable volume for both cooling and heating, with no reheat coil.
-
air_inlet_node_name¶ field Air Inlet Node Name
Parameters: value (str) – value for IDD Field Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_inlet_node_name or None if not set Return type: str
-
air_outlet_node_name¶ field Air Outlet Node Name
The outlet node of the terminal unit.This is also the zone inlet node.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
zone_minimum_air_flow_fraction¶ field Zone Minimum Air Flow Fraction
fraction of maximum air flowvalue <= 1.0Parameters: value (float) – value for IDD Field Zone Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of zone_minimum_air_flow_fraction or None if not set Return type: float
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctVavHeatAndCoolReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat Central air system terminal unit, single duct, variable volume for both cooling and heating, with reheat coil (hot water, electric, gas, or steam).
-
air_inlet_node_name¶ field Air Inlet Node Name
the inlet node to the terminal unit and the damperParameters: value (str) – value for IDD Field Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_inlet_node_name or None if not set Return type: str
-
air_outlet_node_name¶ field Air Outlet Node Name
The outlet node of the terminal unit and the reheat coil.This is also the zone inlet node.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
convergence_tolerance¶ field Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of convergence_tolerance or None if not set Return type: float
-
damper_air_outlet_node_name¶ field Damper Air Outlet Node Name
the outlet node of the damper and the inlet node of the reheat coilthis is an internal node to the terminal unit and connects the damper and reheat coilParameters: value (str) – value for IDD Field Damper Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of damper_air_outlet_node_name or None if not set Return type: str
-
hot_water_or_steam_inlet_node_name¶ field Hot Water or Steam Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Hot Water or Steam Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_or_steam_inlet_node_name or None if not set Return type: str
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_hot_water_or_steam_flow_rate¶ field Maximum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_or_steam_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_reheat_air_temperature¶ field Maximum Reheat Air Temperature
Specifies the maximum allowable supply air temperature leaving the reheat coil.If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.Units: CParameters: value (float) – value for IDD Field Maximum Reheat Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of maximum_reheat_air_temperature or None if not set Return type: float
-
minimum_hot_water_or_steam_flow_rate¶ field Minimum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_or_steam_flow_rate or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
reheat_coil_name¶ field Reheat Coil Name
Parameters: value (str) – value for IDD Field Reheat Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_name or None if not set Return type: str
-
reheat_coil_object_type¶ field Reheat Coil Object Type
Parameters: value (str) – value for IDD Field Reheat Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_object_type or None if not set Return type: str
-
zone_minimum_air_flow_fraction¶ field Zone Minimum Air Flow Fraction
fraction of maximum air flowvalue <= 1.0Parameters: value (float) – value for IDD Field Zone Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of zone_minimum_air_flow_fraction or None if not set Return type: float
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctVavNoReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:VAV:NoReheat Central air system terminal unit, single duct, variable volume, with no reheat coil.
-
air_inlet_node_name¶ field Air Inlet Node Name
Parameters: value (str) – value for IDD Field Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_inlet_node_name or None if not set Return type: str
-
air_outlet_node_name¶ field Air Outlet Node Name
Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
constant_minimum_air_flow_fraction¶ field Constant Minimum Air Flow Fraction
This field is used if the field Zone Minimum Air Flow Input Method is ConstantIf the field Zone Minimum Air Flow Input Method is Scheduled, then this fieldis optional; if a value is entered, then it is used for sizing normal-action reheat coils.If both this field and the following field are entered, the larger result is used.Parameters: value (float) – value for IDD Field Constant Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of constant_minimum_air_flow_fraction or None if not set Return type: float
-
design_specification_outdoor_air_object_name¶ field Design Specification Outdoor Air Object Name
When the name of a DesignSpecification:OutdoorAir object is entered, the terminalunit will increase flow as needed to meet this outdoor air requirement.If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement willbe computed based on the current number of occupants in the zone.At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate.If this field is blank, then the terminal unit will not be controlled for outdoor air flow.Parameters: value (str) – value for IDD Field Design Specification Outdoor Air Object Name Raises: ValueError– if value is not a valid valueReturns: the value of design_specification_outdoor_air_object_name or None if not set Return type: str
-
fixed_minimum_air_flow_rate¶ field Fixed Minimum Air Flow Rate
This field is used if the field Zone Minimum Air Flow Input Method is FixedFlowRate.If the field Zone Minimum Air Flow Input Method is Scheduled, then this fieldis optional; if a value is entered, then it is used for sizing normal-action reheat coils.If both this field and the previous field are entered, the larger result is used.Units: m3/sParameters: value (float) – value for IDD Field Fixed Minimum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of fixed_minimum_air_flow_rate or None if not set Return type: float
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
minimum_air_flow_fraction_schedule_name¶ field Minimum Air Flow Fraction Schedule Name
This field is used if the field Zone Minimum Air Flow Input Method is ScheduledSchedule values are fractions, 0.0 to 1.0.If the field Constant Minimum Air Flow Fraction is blank, then the average of theminimum and maximum schedule values is used for sizing normal-action reheat coils.Parameters: value (str) – value for IDD Field Minimum Air Flow Fraction Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of minimum_air_flow_fraction_schedule_name or None if not set Return type: str
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
zone_minimum_air_flow_input_method¶ field Zone Minimum Air Flow Input Method
Constant = Constant Minimum Air Flow Fraction (a fraction of Maximum Air Flow Rate)FixedFlowRate = Fixed Minimum Air Flow Rate (a fixed minimum air volume flow rate)Scheduled = Scheduled Minimum Air Flow Fraction (a fraction of Maximum Air FlowParameters: value (str) – value for IDD Field Zone Minimum Air Flow Input Method Raises: ValueError– if value is not a valid valueReturns: the value of zone_minimum_air_flow_input_method or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctVavReheat¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:VAV:Reheat Central air system terminal unit, single duct, variable volume, with reheat coil (hot water, electric, gas, or steam).
-
air_inlet_node_name¶ field Air Inlet Node Name
the inlet node to the terminal unit and the damperParameters: value (str) – value for IDD Field Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_inlet_node_name or None if not set Return type: str
-
air_outlet_node_name¶ field Air Outlet Node Name
The outlet node of the terminal unit and the reheat coil.This is also the zone inlet node.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
constant_minimum_air_flow_fraction¶ field Constant Minimum Air Flow Fraction
This field is used if the field Zone Minimum Air Flow Input Method is ConstantIf the field Zone Minimum Air Flow Input Method is Scheduled, then this fieldis optional; if a value is entered, then it is used for sizing normal-action reheat coils.If both this field and the following field are entered, the larger result is used.Parameters: value (float) – value for IDD Field Constant Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of constant_minimum_air_flow_fraction or None if not set Return type: float
-
convergence_tolerance¶ field Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of convergence_tolerance or None if not set Return type: float
-
damper_air_outlet_node_name¶ field Damper Air Outlet Node Name
the outlet node of the damper and the inlet node of the reheat coilthis is an internal node to the terminal unit and connects the damper and reheat coilParameters: value (str) – value for IDD Field Damper Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of damper_air_outlet_node_name or None if not set Return type: str
-
damper_heating_action¶ field Damper Heating Action
Default value: NormalParameters: value (str) – value for IDD Field Damper Heating Action Raises: ValueError– if value is not a valid valueReturns: the value of damper_heating_action or None if not set Return type: str
-
design_specification_outdoor_air_object_name¶ field Design Specification Outdoor Air Object Name
When the name of a DesignSpecification:OutdoorAir object is entered, the terminalunit will increase flow as needed to meet this outdoor air requirement.If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement willbe computed based on the current number of occupants in the zone.At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate.If this field is blank, then the terminal unit will not be controlled for outdoor air flow.Parameters: value (str) – value for IDD Field Design Specification Outdoor Air Object Name Raises: ValueError– if value is not a valid valueReturns: the value of design_specification_outdoor_air_object_name or None if not set Return type: str
-
fixed_minimum_air_flow_rate¶ field Fixed Minimum Air Flow Rate
This field is used if the field Zone Minimum Air Flow Input Method is FixedFlowRate.If the field Zone Minimum Air Flow Input Method is Scheduled, then this fieldis optional; if a value is entered, then it is used for sizing normal-action reheat coils.If both this field and the previous field are entered, the larger result is used.Units: m3/sParameters: value (float) – value for IDD Field Fixed Minimum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of fixed_minimum_air_flow_rate or None if not set Return type: float
-
maximum_air_flow_rate¶ field Maximum Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_flow_fraction_during_reheat¶ field Maximum Flow Fraction During Reheat
Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = ReverseWhen autocalculating, the maximum flow fraction is set to the ratio of0.002032 m3/s-m2 (0.4 cfm/sqft) multiplied by the zone floor area and theMaximum Air Flow Rate.This optional field limits the maximum flow allowed in reheat mode.If this field and the previous field are left blank, the maximum flow will not be limited.At no time will the maximum flow rate calculated here exceed the value ofMaximum Air Flow Rate.Parameters: value (float or “Autocalculate”) – value for IDD Field Maximum Flow Fraction During Reheat Raises: ValueError– if value is not a valid valueReturns: the value of maximum_flow_fraction_during_reheat or None if not set Return type: float or “Autocalculate”
-
maximum_flow_per_zone_floor_area_during_reheat¶ field Maximum Flow per Zone Floor Area During Reheat
Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = ReverseWhen autocalculating, the maximum flow per zone is set to 0.002032 m3/s-m2 (0.4 cfm/sqft)This optional field limits the maximum flow allowed in reheat mode.If this field and the following field are left blank, the maximum flow will not be limited.At no time will the maximum flow rate calculated here exceed the value ofMaximum Air Flow Rate.Units: m3/s-m2Parameters: value (float or “Autocalculate”) – value for IDD Field Maximum Flow per Zone Floor Area During Reheat Raises: ValueError– if value is not a valid valueReturns: the value of maximum_flow_per_zone_floor_area_during_reheat or None if not set Return type: float or “Autocalculate”
-
maximum_hot_water_or_steam_flow_rate¶ field Maximum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_or_steam_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_reheat_air_temperature¶ field Maximum Reheat Air Temperature
Specifies the maximum allowable supply air temperature leaving the reheat coil.If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.Units: CParameters: value (float) – value for IDD Field Maximum Reheat Air Temperature Raises: ValueError– if value is not a valid valueReturns: the value of maximum_reheat_air_temperature or None if not set Return type: float
-
minimum_air_flow_fraction_schedule_name¶ field Minimum Air Flow Fraction Schedule Name
This field is used if the field Zone Minimum Air Flow Input Method is ScheduledSchedule values are fractions, 0.0 to 1.0.If the field Constant Minimum Air Flow Fraction is blank, then the average of theminimum and maximum schedule values is used for sizing normal-action reheat coils.Parameters: value (str) – value for IDD Field Minimum Air Flow Fraction Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of minimum_air_flow_fraction_schedule_name or None if not set Return type: str
-
minimum_hot_water_or_steam_flow_rate¶ field Minimum Hot Water or Steam Flow Rate
Not used when reheat coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_or_steam_flow_rate or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
reheat_coil_name¶ field Reheat Coil Name
Parameters: value (str) – value for IDD Field Reheat Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_name or None if not set Return type: str
-
reheat_coil_object_type¶ field Reheat Coil Object Type
Parameters: value (str) – value for IDD Field Reheat Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of reheat_coil_object_type or None if not set Return type: str
-
zone_minimum_air_flow_input_method¶ field Zone Minimum Air Flow Input Method
Constant = Constant Minimum Air Flow Fraction (a fraction of Maximum Air Flow Rate)FixedFlowRate = Fixed Minimum Air Flow Rate (a fixed minimum air volume flow rate)Scheduled = Scheduled Minimum Air Flow Fraction (a fraction of Maximum Air FlowParameters: value (str) – value for IDD Field Zone Minimum Air Flow Input Method Raises: ValueError– if value is not a valid valueReturns: the value of zone_minimum_air_flow_input_method or None if not set Return type: str
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.AirTerminalSingleDuctVavReheatVariableSpeedFan¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan Central air system terminal unit, single duct, variable volume, with reheat coil (hot water, electric, gas, or steam) and variable-speed fan. These units are usually employed in underfloor air distribution (UFAD) systems where the air is supplied at low static pressure through an underfloor plenum. The fan is used to control the flow of conditioned air that enters the space.
-
air_inlet_node_name¶ field Air Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_inlet_node_name or None if not set Return type: str
-
air_outlet_node_name¶ field Air Outlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Air Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_outlet_node_name or None if not set Return type: str
-
availability_schedule_name¶ field Availability Schedule Name
Availability schedule name for this system. Schedule value > 0 means the system is available.If this field is blank, the system is always available.Parameters: value (str) – value for IDD Field Availability Schedule Name Raises: ValueError– if value is not a valid valueReturns: the value of availability_schedule_name or None if not set Return type: str
-
fan_name¶ field Fan Name
Parameters: value (str) – value for IDD Field Fan Name Raises: ValueError– if value is not a valid valueReturns: the value of fan_name or None if not set Return type: str
-
fan_object_type¶ field Fan Object Type
Parameters: value (str) – value for IDD Field Fan Object Type Raises: ValueError– if value is not a valid valueReturns: the value of fan_object_type or None if not set Return type: str
-
heating_coil_air_inlet_node_name¶ field Heating Coil Air Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Heating Coil Air Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of heating_coil_air_inlet_node_name or None if not set Return type: str
-
heating_coil_name¶ field Heating Coil Name
Parameters: value (str) – value for IDD Field Heating Coil Name Raises: ValueError– if value is not a valid valueReturns: the value of heating_coil_name or None if not set Return type: str
-
heating_coil_object_type¶ field Heating Coil Object Type
Parameters: value (str) – value for IDD Field Heating Coil Object Type Raises: ValueError– if value is not a valid valueReturns: the value of heating_coil_object_type or None if not set Return type: str
-
heating_convergence_tolerance¶ field Heating Convergence Tolerance
Default value: 0.001Parameters: value (float) – value for IDD Field Heating Convergence Tolerance Raises: ValueError– if value is not a valid valueReturns: the value of heating_convergence_tolerance or None if not set Return type: float
-
hot_water_or_steam_inlet_node_name¶ field Hot Water or Steam Inlet Node Name
This field is not really used and will be deleted from the object.The required information is gotten internally ornot needed by the program.Parameters: value (str) – value for IDD Field Hot Water or Steam Inlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of hot_water_or_steam_inlet_node_name or None if not set Return type: str
-
maximum_cooling_air_flow_rate¶ field Maximum Cooling Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Cooling Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_cooling_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_heating_air_flow_rate¶ field Maximum Heating Air Flow Rate
Units: m3/sParameters: value (float or “Autosize”) – value for IDD Field Maximum Heating Air Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_heating_air_flow_rate or None if not set Return type: float or “Autosize”
-
maximum_hot_water_or_steam_flow_rate¶ field Maximum Hot Water or Steam Flow Rate
Not used when heating coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float or “Autosize”) – value for IDD Field Maximum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of maximum_hot_water_or_steam_flow_rate or None if not set Return type: float or “Autosize”
-
minimum_hot_water_or_steam_flow_rate¶ field Minimum Hot Water or Steam Flow Rate
Not used when heating coil type is gas or electricUnits: m3/sIP-Units: gal/minParameters: value (float) – value for IDD Field Minimum Hot Water or Steam Flow Rate Raises: ValueError– if value is not a valid valueReturns: the value of minimum_hot_water_or_steam_flow_rate or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
zone_minimum_air_flow_fraction¶ field Zone Minimum Air Flow Fraction
fraction of cooling air flow ratevalue <= 1.0Parameters: value (float) – value for IDD Field Zone Minimum Air Flow Fraction Raises: ValueError– if value is not a valid valueReturns: the value of zone_minimum_air_flow_fraction or None if not set Return type: float
-
-
class
pyidf.zone_hvac_air_loop_terminal_units.ZoneHvacAirDistributionUnit¶ Bases:
pyidf.helper.DataObjectCorresponds to IDD object ZoneHVAC:AirDistributionUnit Central air system air distribution unit, serves as a wrapper for a specific type of air terminal unit. This object is referenced in a ZoneHVAC:EquipmentList.
-
air_distribution_unit_outlet_node_name¶ field Air Distribution Unit Outlet Node Name
Parameters: value (str) – value for IDD Field Air Distribution Unit Outlet Node Name Raises: ValueError– if value is not a valid valueReturns: the value of air_distribution_unit_outlet_node_name or None if not set Return type: str
-
air_terminal_name¶ field Air Terminal Name
Parameters: value (str) – value for IDD Field Air Terminal Name Raises: ValueError– if value is not a valid valueReturns: the value of air_terminal_name or None if not set Return type: str
-
air_terminal_object_type¶ field Air Terminal Object Type
Parameters: value (str) – value for IDD Field Air Terminal Object Type Raises: ValueError– if value is not a valid valueReturns: the value of air_terminal_object_type or None if not set Return type: str
-
constant_downstream_leakage_fraction¶ field Constant Downstream Leakage Fraction
value <= 0.3Parameters: value (float) – value for IDD Field Constant Downstream Leakage Fraction Raises: ValueError– if value is not a valid valueReturns: the value of constant_downstream_leakage_fraction or None if not set Return type: float
-
name¶ field Name
Parameters: value (str) – value for IDD Field Name Raises: ValueError– if value is not a valid valueReturns: the value of name or None if not set Return type: str
-
nominal_upstream_leakage_fraction¶ field Nominal Upstream Leakage Fraction
fraction at system design Flow; leakage Flow constant, leakage fractionvaries with variable system Flow Rate.value <= 0.3Parameters: value (float) – value for IDD Field Nominal Upstream Leakage Fraction Raises: ValueError– if value is not a valid valueReturns: the value of nominal_upstream_leakage_fraction or None if not set Return type: float
-